Analisis Moisture Content dan Dew Point Gas SF6 Pada PMT di Gardu Induk Cigereleng PT PLN (Persero) Transmisi Jawa Bagian Tengah

Penulis

  • ANDRI SEWAGETRA Teknik Elektro Institut Teknologi Nasional Bandung
  • DINI FAUZIAH Teknik Elektro Institut Teknologi Nasional Bandung

Abstrak

ABSTRAK

Metode yang dilakukan penulis adalah menganalisis hasil nilai uji dewpoint dan moisture content berdasarkan standar yang ditentukan dan menganalisa pengaruh suhu lingkungan terhadap nilai dewpoint. Pada penelitian ini penulis mendapatkan hasil nilai uji dewpoint dan moisture content     pada PMT bay KOPEL (dewpoint -28 °C & Moisture Contet 461 PPMV) & bay CKLNG 1 (dewpoint -30 °C & Moisture Contet 223PPMV) keduanya masih berada dalam batas standar internasional yang digunakan dimana untuk dewpoint <-5°C dan Moisture Content < 3960 PPMV. Kemudian hasil nilai perhitungan dewpoint pada suhu berbeda (20°C) didpatkan hasil nilai uji yang jauh lebih rendah, dimana untuk pada bay KOPEL nilai dewpoint -9°C dan pada bay CKLNG 1 nilai dewpoint - 17°C. Dapat disimpulkan bahwa suhu lingkungan sekitar dapat mempengaruhi nilai dewpoint Gas  dalam PMT, semakin rendah suhu lingkunga maka akan semakin besar nilai dewpoint pada PMT yang artinya mendekati batas nilai standar gas dalam keadaan baik.

Kata kunci: SF6, Moisture Content, Dewpoint, IEEE 1125 tahun 1993, Suhu

 

ABSTRACT

The method used by the author is to analyze the results of the dewpoint test value and moisture content based on the specified standard and analyze the effect of environmental temperature on the dewpoint value. In this study, the authors obtained the results of the dewpoint and moisture content test values ​​on PMT bay KOPEL (dewpoint -28 °C & Moisture Contet 461 PPMV) & bay CKLNG 1 (dewpoint -30 °C & Moisture Contet 223PPMV) both of which were still within the limits of international standards. which is used where for dewpoint <-5°C and Moisture Content < 3960 PPMV. Then the results of the calculated dewpoint values ​​at different temperatures (20°C) obtained a much lower test value, where for the KOPEL bay the dewpoint value was -9°C and in the CKLNG 1 bay the dewpoint value was - 17°C. It can be concluded that the ambient temperature can affect the dewpoint value of gas in PMT, the lower the ambient temperature, the greater the dewpoint value in PMT, which means that it is close to the standard value of the gas in good condition

Keywords: SF6, Moisture Content, Dewpoint, IEEE 1125 tahun 1993, temperature

Unduhan

Diterbitkan

2022-01-28