Analisis Perbandingan Arus Bocor Isolator Disc porcelain secara Tunggal dan Ganda Paralel

Authors

  • ADITYA JAYA PRATAMA Fakultas Teknik Industri Institut Teknologi Nasional Bandung
  • WALUYO Fakultas Teknik Industri Institut Teknologi Nasional Bandung

Keywords:

Insulator, Temperature, Humidity, Leakage Current, Environmental, Isolator, Suhu, Kelembapan, Arus Bocor, Lingkungan

Abstract

Insulators are usually installed in open spaces, so it is necessary to test the  insulator with various installation conditions and different times. The purpose of  this activity is to obtain the impact of dominant environmental factors on  insulator performance. This research was held for 35 days and took into attention  the temperature and humidity conditions. The insulator installation uses a disk  type insulator and uses a 20kΩ resistor. Single and parallel insulator leakage  current data obtained in the morning 130,200µA and 289,500µA, temperature  19.6℃ and humidity 84.6%, in the afternoon 117,850µA and 173,000µA,  temperature 42℃ and humidity 32.3%, in the evening 209,500µA and  452,000µA, temperature 22.2℃ and humidity 92.3%. When the environmental temperature is getting bigger, the leakage current that occurs in the insulator is  getting smaller, while when the environmental humidity is getting bigger, the leakage current that occurs in the insulator is getting bigger. The most significant and dominant parameter in forming the leakage current of both insulators is temperature-humidity with the highest correlation value.  Keywords: Insulator, Temperature, Humidity, Leakage Current, Environmental

Abstrak

Isolator biasanya dipasang diruang terbuka, maka perlu di lakukan pengetesan terhadap isolator dengan berbagai macam kondisi pemasangan dan waktu yang berbeda. Tujuan dari kegiatan ini untuk memperoleh pengaruh faktor lingkungan yang dominan terhadap kinerja isolator. Penelitian ini dilakukan selama 35 hari serta memperhatikan kondisi suhu dan kelembapan. Pemasangan isolator mengggunakan isolator jenis cakram serta menggunakan resistor sebesar 20kΩ. Data arus bocor isolator tunggal dan paralel yang didapat saat pagi hari 130,200 µA dan 289,500μA, suhu 19,6℃ dan kelembapan 84,6%, saat siang hari 117,850μA dan 173,000μA, suhu 42℃ dan kelembapan 32,3%, saat malam hari 209,500μA dan 452,000μA, suhu 22,2℃ dan kelembapan 92,3%. Pada saat suhu lingkungan semakin besar maka arus bocor yang terjadi pada isolator semakin kecil, sedangkan saat kelembapan lingkungan semakin besar maka arus bocor yang terjadi pada isolator semakin besar. Parameter yang paling berpengaruh dan dominan dalam pembentukan arus bocor kedua isolator adalah suhu kelembapan dengan nilai korelasi tertinggi. Kata kunci: Isolator, Suhu, Kelembapan, Arus Bocor, Lingkungan

Published

2024-12-09